R7550A-ST1000
ACOLAN® COPPER
Applications
- High speed data transmission cables are designed for backbone distribution local computer networks.
- These cables are permitted the protocol supported by the class E.
- They are characterized of up to 400 MHz.
- They are compatibles with PoE & PoE+, UPoE applications.
General characteristics
|
Solid annealed red copper wire, AWG 24 |
|
Cable assembly in Twisted Pairs |
|
Symetrical cross separator |
|
4 pairs screening assembly |
|
LSOH-FR : Low Smoke « Zero » Halogen - Flame Retardant |
Designation ACOLAN |
Ref. |
Colour |
Diameter |
Weight |
Superior calorificcapacity (PCS) |
Max pulling tension |
|
mm |
Kg/km |
MJ/km |
KWh/m |
N |
|||
400 UU 4P LSOH-FR |
R7550A-S |
Ivory |
5.30 |
33 |
394 |
0.110 |
90 |
Characteristics |
Values |
|
Bending radius |
Dynamic (installation) |
≥ 45 mm |
Static (installed) |
≥ 23 mm |
|
Temperature range |
In service |
- 20°C at + 60°C |
At the installation |
0°C at + 50°C |
|
Transport and storage |
0°C at + 50°C |
Transmission characteristics at 20° C
Characteristics |
Values |
||
Complete conductor resistance |
|
≤ 190 Ω / km |
|
Resistance unbalance |
|
≤ 2 % |
|
Dielectric strength |
Continuous current |
1kV during1 minute = No breakdown |
|
Insulation resistance |
(500 V) |
≥ 5000 MΩ . km |
|
Capacitance unbalance |
Real-ground |
≤ 1600 pF / km |
|
Characteristic impedance |
at 100 MHz |
100 ± 5 Ω |
|
Velocity |
nominal |
66 % |
|
Coupling attenuation |
|
≥ 40 dB |
TYPE 3 |
Segregation classification acc. to EN 50174-2 |
|||
|
‘’c’’ |
Frequency (MHz) |
4 | 10 | 20 | 62.5 | 100 | 250 | 300** | 400** | |
Attenuation (dB/100m) | Typical value | 3.7 | 5.8 | 8.4 | 15.0 | 19.2 | 31.5 | 34.5 | 42 |
Imposition (max)* | 3.8 | 6 | 8.5 | 8.5 | 19.9 | 33 | - | - | |
Next (dB) | Typical value | 69 | 63 | 59 | 51 | 48 | 42 | 41 | 38 |
Imposition (min)* | 65.3 | 59.3 | 54.8 | 47.4 | 44.3 | 38.3 | - | - | |
ACR (dB) | Typical value | 65.3 | 57.2 | 50.6 | 36 | 28.8 | 10.5 | 6.5 | |
Imposition (min)* | 61.5 | 53.3 | 46.3 | 31.9 | 24.4 | 5.3 | - | - | |
PS Next (dB) | Typical value | 66 | 60 | 56 | 48 | 45 | 39 | 38 | 35 |
Imposition (min)* | 63.3 | 57.3 | 52.8 | 45.4 | 42.3 | 36.3 | - | - | |
ELFEXT (dB/100 m) | Typical value | 73 | 65 | 59 | 49 | 45 | 37 | 35 | 32 |
Imposition (min)* | 58 | 50 | 44 | 34.1 | 30 | 22 | - | - | |
PS ELFEXT (dB/100 m) | Typical value | 70 | 62 | 56 | 46 | 42 | 34 | 32 | 29 |
Imposition (min)* | 55 | 47 | 41 | 31.1 | 27 | 19 | - | - | |
Return Loss (dB) | Typical value | 27 | 27 | 27 | 25.8 | 25 | 22 | 22 | 21 |
Imposition (min)* | 23 | 25 | 25 | 21.5 | 20.1 | 17.3 | - | - |
Norms and standards
400 MHz
Applications
- IEEE 802.3: 10Base-T; 100Base-TX; 1000Base-T ;
- 1000Base-T ; 2,5G Base-T
- IEEE 802.3 af (PoE) / 802.3 at (PoE+)
- IEEE 802.5 / FDDI / ATM / RNIS
Cables
- IEC 61156-5 ed.2 / EN 50288-6-1
Cabling system standard
- ISO/IEC 11801 2nd ed. / EN 50173-1 / TIA-568.2-D
Cabling system installation standard
- EN 50174
Directive / Regulation
- RoHS 2011/65/UE
- REACH 1907/2006/EC
Europe
Type |
Euroclass |
Standards |
Declaration of performance |
|
4P |
Eca |
IEC 60332-1 |
Outside Europe
No flame propagation |
IEC 60332-1 / EN 60332-1 |
Low smoke opacity |
IEC 61034-2 / EN 61034-2 |
Low gas corrosivity |
IEC 60754-2 / EN 60754-2 |
Low toxicity |
IEC 60754-1 / EN 60754-1 |
Recommendations
Type |
References |
Individual |
Expedition |
||||
Type |
Weight |
EAN code |
Quantity |
Weight |
EAN code |
||
4P LSOH |
R7550A - SB305 |
Acopack of 305 m |
10.70 kg |
3700223681457 |
24 boxes |
280 kg |
3700223681464 |
R7550A – ST1000 |
Drum of 1000 m |
35 kg |
3700223681624 |
18 drums |
652 kg |
3700223681631 |
|
R7550A – ST4000 |
Drum of 4000 m |
146 kg |
3700223681600 |
1 drums |
164 kg |
3700223681600 |