R8436A-T500
ACOLAN® COPPER FIREPROTECT
Applications
- 10 Gigabit high speed data transmission cables are designed for horizontal cable distribution local computer networks.
- These cables allow the use of the protocol supported by the F class for the 10 GBASE-T applications.
- They are characterized of up to 1000 MHz.
- They are compatibles with PoE & PoE+, UPoE & 4PPoE (PoE++) applications.
See our White Paper on installation conditions on www.acome.com also available on demand.
General characteristics
|
Solid annealed red copper wire, AWG 23 Foam skin Pe insulation Ø ≤ 1.40 mm |
|
Cable assembly in Twisted Pairs |
|
Pet/Alu foil around each pair |
|
4 pairs screening assembly |
|
Tinned copper braid |
|
LSOH-FR : Low Smoke « Zero » Halogen - Flame Retardant |
Designation ACOLAN FIREPROTECT |
Réf. |
Colour |
Diameter |
Weight |
PCS (superior calorific capacity) |
Max. pulling tension |
|
mm |
Kg/km |
MJ/km |
KWh/m |
N |
|||
1000 SF-P 4P LSOH-FR |
R8436A |
Yellow |
7,70 |
63 |
597 |
0.166 |
95 |
Characteristics |
Values |
|
Bending radius |
Dynamic (installation) |
≥ 60 mm |
Static (installed) |
≥ 30 mm |
|
Temperature range |
In service |
- 20°C at + 60°C |
At the installation |
0°C at + 50°C |
|
Transport and storage |
0°C at + 50°C |
Characteristics |
Values |
||
Complete conductor resistance |
|
≤ 146.4 Ω / km |
|
Resistance unbalance |
|
≤ 2 % |
|
Dielectric strength |
Continuous current |
1kV during1 minute = No breakdown |
|
Insulation resistance |
(500 V) |
≥ 5000 MΩ . km |
|
Capacitance unbalance |
Real-ground |
≤ 1600 pF / km |
|
Characteristic impedance |
at 100 MHz |
100 ± 5 Ω |
|
Velocity |
nominal |
78 % |
|
Coupling attenuation |
|
≥ 85 dB |
TYPE 1 |
Transfer impedance |
At 1 MHz |
≤ 8 mΩ / m |
GRADE 1
|
At 10 MHz |
≤ 8 mΩ / m |
||
At 30 MHz |
≤ 10 mΩ / m |
||
At 100 MHz |
≤ 20 mΩ / m |
||
Segregation classification acc. To EN 50174-2 |
|
“d” |
Frequency (MHz) | 4 | 10 | 20 | 62.5 | 100 | 250 | 300 | 600 | 1000** | |
Attenuation(dB/100m) | Typical value | 3.6 | 5.5 | 7.9 | 14.5 | 18.5 | 29.6 | 32.8 | 47.6 | 63.8 |
Imposition (max)* | 3.7 | 5.9 | 8.3 | 14.9 | 19 | 31 | 34.2 | 50.1 | - | |
Next (dB) | Typical value | 95 | 95 | 95 | 95 | 95 | 88 | 87 | 82 | 78 |
Imposition (min)* | 78 | 78 | 78 | 75 | 72 | 66 | 65 | 61 | - | |
PS Next (dB) | Typical value | 92 | 92 | 92 | 92 | 92 | 85 | 84 | 79 | 75 |
Imposition (min)* | 75 | 75 | 75 | 72 | 69 | 63 | 62 | 58 | - | |
ELFEXT (dB/100 m) | Typical value | 85 | 85 | 84 | 82 | 78 | 70 | 67 | 55 | 52 |
Imposition (min)* | 78 | 74 | 68 | 58 | 54 | 46 | 44 | 38 | - | |
PS ELFEXT (dB/100 m) | Typical value | 82 | 82 | 81 | 79 | 75 | 67 | 64 | 52 | 49 |
Imposition (min)* | 75 | 71 | 65 | 55 | 51 | 43 | 41 | 35 | ||
Return Loss (dB) | Typical value | 26 | 26 | 26 | 26 | 24 | 22 | 21 | 19 | 18 |
Imposition (min)* | 23 | 25 | 25 | 21.5 | 20.1 | 17.3 | 17.3 | 17.3 | - |
Norms and standards
Applications
- IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T; 2,5G Base-T,
- 5G Base-T, 10G Base-T
- IEEE 802.3 af (PoE) / 802.3 at (PoE+) / 802.3 bt (4PPoE 90W)
- IEEE 802.5 / FDDI / ATM / RNIS
Cable
IEC 61156-5 ed.2 / EN 50288-4-1
Cabling system standard
ISO/IEC 11801 2nd ed. / EN 50173-1
Cabling system installation standard
EN 50174
Directive / Regulation
RoHS 2011/65/UE
REACH 1907/2006/EC
Europe
Type |
Euroclass |
Standards |
Declaration of performance |
|
4P |
Cca-s1,d2,a1 |
IEC 60332-1, EN 50399, IEC 60754-2 |
Outside Europe
No flame propagation |
IEC 60332-1 / EN 60332-1 |
No fire propagation |
IEC 60332-3-24 / EN 60332-3-24 |
Low smoke opacity |
IEC 61034-2 / EN 61034-2 |
Low gas corrosivity |
IEC 60754-2 / EN 60754-2 |
Low toxicity |
IEC 60754-1 / EN 60754-1 |
Recommendations
Type |
References |
Individual |
Expedition |
||||
Type |
Weight |
EAN code |
Type |
Weight |
EAN code |
||
4P LSOH-FR |
R8436A-T500 |
KT Drum of 500 m |
34 kg |
3700223699513 |
18 drums |
615kg |
3700223699506 |
R8436A-T1000 |
XL Drum of 1000 m |
68 kg |
3700223699537 |
4 drums |
284kg |
3700223699520 |