R7585A-T500
ACOLAN® COPPER FIREPROTECT
Applications
- 10 Gigabit high speed data transmission cables are designed for horizontal cable distribution local computer networks.
- These cables allow the use of the protocol supported by the F class for the 10GBASE-T applications.
- They are characterized of up to 1000 MHz.
- They are compatibles with PoE & PoE+, UPoE & 4PPoE (PoE++) applications.
General characteristics
|
Solid annealed red copper wire, AWG 23 Foam skin Pe insulation Æ ≤ 1.45 mm |
|
Cable assembly in Twisted Pairs |
|
Pet/Alu foil around each pair |
|
4 pairs screening assembly |
|
Pet/Alu foil and tinned drain wire AWG26 |
|
LSOH-FR : Low Smoke « Zero » Halogen - Flame Retardant |
Designation ACOLAN |
Ref. |
Colour |
Diameter |
Weight |
Superior calorificcapacity (PCS) |
Max pulling tension |
|
mm |
Kg/km |
MJ/km |
KWh/m |
N |
|||
1000 FF 4P LSOH-FR |
R7585A |
Green (RAL 6024) |
7.50 |
55 |
550 |
0.153 |
95 |
1000 FFD 2x4P LSOH-FR
|
R7586A |
Green (RAL 6024) |
7.50x15.50 |
105 |
1125 |
0.312 |
190 |
*EC verified : structure 4P & 2x4P
Characteristics |
Values |
|
Bending radius |
Dynamic (installation) |
≥ 60 mm |
Static (installed) |
≥ 30 mm |
|
Temperature range |
In service |
- 20°C at + 60°C |
At the installation |
0°C at + 50°C |
|
Transport and storage |
0°C at + 50°C |
Frequency (MHz) |
|
4 |
10 |
20 |
62.5 |
100 |
250 |
300 |
600 |
1000** |
Attenuation (dB/100m) |
Typical value |
3.6 |
5.5 |
7.9 |
14.5 |
18.5 |
29.6 |
32.8 |
47.6 |
63.8 |
Imposition (max)* |
3.7 |
5.9 |
8.3 |
14.9 |
19 |
31 |
34.2 |
50,1 |
- |
|
Next (dB) |
Typical value |
95 |
95 |
95 |
95 |
95 |
88 |
87 |
82 |
78 |
Imposition (min)* |
78 |
78 |
78 |
75 |
72 |
66 |
65 |
61 |
- |
|
PS Next (dB) |
Typical value |
92 |
92 |
92 |
92 |
92 |
85 |
84 |
79 |
75 |
Imposition (min)* |
75 |
75 |
75 |
72 |
69 |
63 |
62 |
58 |
- |
|
ELFEXT (dB/100 m) |
Typical value |
85 |
85 |
84 |
82 |
78 |
70 |
67 |
55 |
52 |
Imposition (min)* |
78 |
74 |
68 |
58 |
54 |
46 |
44 |
38 |
- |
|
PS ELFEXT (dB/100 m) |
Typical value |
82 |
82 |
81 |
79 |
75 |
67 |
64 |
52 |
49 |
Imposition (min)* |
75 |
71 |
65 |
55 |
51 |
43 |
41 |
35 |
|
|
Return Loss (dB) |
Typical value |
26 |
26 |
26 |
26 |
24 |
22 |
21 |
19 |
18 |
Imposition (min)* |
23 |
25 |
25 |
21.5 |
20.1 |
17.3 |
17.3 |
17.3 |
- |
* Category 7 according IEC 61156-5
** For information only
Electrical characteristics at 20°C (68°F)
Characteristics |
Values |
||
Complete conductor resistance |
|
≤ 146.4Ω / km |
|
Resistance unbalance |
|
≤ 2 % |
|
Dielectric strength |
Continuous current |
1kV during1 minute = No breakdown |
|
Insulation resistance |
(500 V) |
≥ 5000 MΩ . km |
|
Capacitance unbalance |
Real-ground |
≤ 1600 pF / km |
|
Characteristic impedance |
at 100 MHz |
100 ± 5 Ω |
|
Velocity |
nominal |
78 % |
|
Coupling attenuation |
|
≥ 70 dB |
TYPE 1b |
Transfer impedance |
At 1 MHz |
≤ 30 mΩ / m |
GRADE 2 |
At 10 MHz |
≤ 30 mΩ / m |
||
At 30 MHz |
≤ 50 mΩ / m |
||
At 100 MHz |
≤ 100 mΩ / m |
||
Segregation classification acc. to EN 50174.2 |
|
‘’c’’ |
Norms and standards
EC
Applications
IEEE 802.3 :10Base-T; 100Base-TX;1000Base-T; 2,5GBase-T ; 5GBase-T ; 10GBase –T
IEEE 802.3 af (PoE) / 802.3 at (PoE+) / 802.3 bt (4PPoE 90W)
IEEE 802.5 / FDDI / ATM / RNIS
Cables
IEC 61156-5 ed.2 / EN 50288-4-1
Cabling system standard
ISO/IEC 11801 2nd ed. / EN 50173-1 / EN 50173-5
Cabling system installation standard
EN 50174
Directive / Regulation
RoHS 2011/65/UE
REACH 1907/2006/EC
Europe
Type |
Euroclass |
Standards |
Declaration of performance |
|
4P |
Cca-s1a,d1,a1 |
IEC 60332-1, EN 50399, IEC 60754-2 |
17FFTP010 |
|
2x4P |
18FFTP009 |
Outside Europe
No flame propagation |
IEC 60332-1 / EN 60332-1 |
Low smoke opacity |
IEC 61034-2 / EN 61034-2 |
Low gas corrosivity |
IEC 60754-2 / EN 60754-2 |
Low toxicity |
IEC 60754-1 / EN 60754-1 |
Recommendations
Type |
References |
Individual |
Expedition |
||||
Type |
Weight |
EAN code |
Quantity |
Weight |
EAN code |
||
4P LSOH-FR |
R7585A – T500 |
Drum KT of 500 m |
30 kg |
3700223696246 |
18 drums |
545 kg |
3700223696253 |
R7585A-T1000 |
Drum XL of 1000 m |
58 kg |
3700223696239 |
4 drums |
255 kg |
3700223696222 |
|
2x4P LSOH-FR |
R7586A – T500 |
Drum XL of 500 m |
58 kg |
3700223696260 |
4 drums |
245 kg |
3700223696277 |
R7586A-T1000 |
Drum AC of 1000 m |
115 kg |
------------- |
4 drums |
475 kg |
------------- |